Revision 1.5 Page 9 of 19
Ensure that all power is
switched off before
installing or maintaining
this product
Mercury 2 & Intuitive Mercury Mini-Pack Installation Guide
www.resourcedm.com
P-65
P-69
Stage 4 Relay 1
Stage 4 Relay 5
0 = Off. 1 = On
1
0
P-70
P-74
Stage 5 Relay 1
Stage 5 Relay 5
0 = Off. 1 = On
1
0
P-20
Alarm Delay
00:00 - 99:00
01:00
mm:ss
05:00
P-21
HP Alarm
-3.4 to 50.0 (-49.3 to 725)
0.1
Bar/Psi
4.1 (59)
P-22
LP Alarm
-3.4 to 50.0 (-49.3 to 725)
0.1
Bar/Psi
0.6 (9)
P-23
LP Shutdown
-3.4 to 50.0 (-49.3 to 725)
0.1
Bar/Psi
0.4 (6)
P-30
P-34
Status Fault 1 (Pack)
Status Fault 5 (Pack)
0 = Unused, 1 = Probe
2 = Comp N/O, 3 = Comp N/C
4 = Gen N/O, 5 = Gen N/C
6 = Std N/O, 7 = Std N/C
1
0
P-30
P-34
Status Fault 1 (Condenser)
Status Fault 5 (Condenser)
0 = Unused, 1 = Probe
2 = Cond N/O, 3 = Cond N/C
4 = Gen N/O, 5 = Gen N/C
6 = Std N/O, 7 = Std N/C
1
0
P-40
Status Fault Delay
00:00 - 60:00
00:01
mm:ss
00:10
P-41
General Fault Delay
00:00 - 60:00
00:01
mm:ss
00:10
dFLt
Restore default values
* Span and Offset allows for the full range of the transducer to be used by the controller.
Span is the full range of the transducer
Offset is the value below zero.
Example: Danfoss AKS 33 with range: -1 bar to 12 bar
Span would be 190 (13 bar)
Offset would be -15 (-1 bar)