Mercury Plant Controller Installation Guide
Example: Danfoss AKS 33 with range: -1 bar to 12 bar
Span would be 190 (13 bar)
Offset would be -15 (-1 bar)
**Run smallest = on : - When all compressors are off (because the target pressure has been satisfied) the
controller, when the pressure rises, will always turn on the smallest compressor after the variable output has
reached 100%. If the ASC timer is running for the smallest compressor, the controller will NOT bring on any other
available compressors, the variable output will remain at 100% and the controller will wait until the ASC timer has
elapsed and then turn on the smallest.
Please note that this is true for any pressure condition.